{"id":"CVE-2025-11784","details":"Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'ShowMeterDatabase()' function, there is an unlimited user input that is copied to a fixed-size buffer via 'sprintf()'. The 'GetParameter(meter)' function retrieves the user input, which is directly incorporated into a buffer without size validation. An attacker can provide an excessively large input for the 'meter' parameter.","modified":"2026-03-12T17:35:18.124115Z","published":"2025-12-02T13:15:49.977Z","references":[{"type":"ADVISORY","url":"https://www.incibe.es/en/incibe-cert/notices/aviso-sci/multiple-vulnerabilities-circutor-products-0"}],"affected":[{"database_specific":{"source":"https://storage.googleapis.com/cve-osv-conversion/osv-output/CVE-2025-11784.json","unresolved_ranges":[{"events":[{"introduced":"0"},{"last_affected":"9.0.2"}]},{"events":[{"introduced":"0"},{"last_affected":"9.0.2"}]}]}}],"schema_version":"1.7.3","severity":[{"type":"CVSS_V3","score":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"}]}